{"id":26468,"date":"2023-03-24T09:41:57","date_gmt":"2023-03-24T08:41:57","guid":{"rendered":"https://www.istec.com/ar/?p=26468"},"modified":"2026-07-24T10:41:41","modified_gmt":"2026-07-24T08:41:41","slug":"customer-reference-thyssengas-overspeed-detection-system-replacement","status":"publish","type":"post","link":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/","title":{"rendered":"Customer reference Thyssengas: Overspeed detection system replacement"},"content":{"rendered":"<h2><span style=\"color: #999999;\"><em>Proof-testing overspeed detection systems (ODS) and replacing Jaquet FT3000 ODS with Istec SpeedSys 300 at a gas compressor station in Germany</em></span></h2>\n<p><span class=\"large-p\">Thyssengas is one of the leading gas transmission system operators in Germany. At their plant in Elten they operate two gas turbines that drive two gas compressors to maintain the pressure of the gas network, one for low and one for high pressure applications.</span></p>\n<p><span class=\"large-p\">The Jaquet FT3000 overspeed detection system (ODS) was used for overspeed protection on the gas turbines. In cooperation with the TÜV, Istec annually performs the proof-tests of the FT3000 systems to maintain the safety integrity and adhere to the safety standards.</span></p>\n<p><span class=\"large-p\">Due to the recent obsolescence of the Jaquet FT3000 system, spare parts are no longer available. Thyssengas decided to replace the system with the Istec SpeedSys 300 (SIL 3).</span></p>\n<h2>ODS proof-testing service</h2>\n<p>Bringing a turbine in an actual overspeed situation is not an option due to safety reasons. Instead, overspeed situations are simulated to proof-test the ODS. Istec uses the <span class=\"alt-link\"><a href=\"https://www.istec.com/ar/product/frequency-generator-ist-101/\">IST-101 3-channel frequency generator</a></span> to proof-test the full loop, including sensors, cabling and the overspeed system (terminal connection). The probe adapter functions as a 3-channel pole wheel, to make the sensor detect (simulated) gear teeth. When actuated on the terminal connections of the rack, the IST-101 simulates the sensor itself.</p>\n<p>The amount of speed wheel teeth and the rotational speed are simulated by using the IST-101. As the device has three channels, all sensors of the 2oo3 configuration can be tested individually, but various combinations can also be simulated. This is crucial for a full proof-test. To facilitate a full-proof test, several steps are taken:</p>\n<ol>\n<li>The sensors are tested separately (e.g., first sensor A, then B, then C).</li>\n<li>The sensors are tested in pairs (e.g., AB, then AC, then BC), to simulate 2oo3 voting.</li>\n<li>A cable breach is simulated by disconnecting a sensor cable while simultaneously simulating an overspeed signal to another sensor.</li>\n</ol>\n<h2>Replacing the obsolete FT3000 ODS with the SpeedSys 300 ODS</h2>\n<p>Thyssengas wanted to replace the current Jaquet FT3000 ODS with the SpeedSys 300 ODS, while maintaining the existing infrastructure. This meant that the SpeedSys 300 units, which are normally DIN-rail mounted, had to be installed in 19” racks in a 2oo3 configuration. The existing DSF 1210 Hall-effect speed probes were also kept in use.</p>\n<figure id=\"attachment_26470\" aria-describedby=\"caption-attachment-26470\" style=\"width: 730px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"size-large wp-image-26470\" src=\"https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x317.jpg\" alt=\"\" width=\"730\" height=\"317\" srcset=\"https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x317.jpg 730w, https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-300x130.jpg 300w, https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-768x334.jpg 768w, https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-1536x668.jpg 1536w, https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-2048x890.jpg 2048w\" sizes=\"auto, (max-width: 730px) 100vw, 730px\" /><figcaption id=\"caption-attachment-26470\" class=\"wp-caption-text\">Figure 1. The old FT3000 rack, which included 6x FTFU 3024 overspeed protection modules, 6x FTV 3090 relay modules, 1x FTM 3020 card to reset the relay cards after a trip initiation, and 1x FTK 3072 communication module.</figcaption></figure>\n<p>Istec has pre-engineered the new SpeedSys 300 racks to be built into the existing cabinet, where the FT3000 rack was previously installed. The new installation includes a reset function to reset the SpeedSys 300 units after a trip has been initiated.</p>\n<p><span class=\"alt-link\"><a href=\"https://www.istec.com/ar/product/speedsys-300/\" target=\"_blank\" rel=\"noopener\">Learn more about the Istec SpeedSys 300 »</a></span></p>\n<p><a href=\"https://www.istec.com/ar/product/ft3000-rack-replacement/\" target=\"_blank\" rel=\"noopener\"><span class=\"alt-link\">Learn more about the SpeedSys rack installation » </span></a></p>\n<h2><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter wp-image-35874 size-large\" src=\"https://img.istec.com/2026/04/a3a71656-thyssengas-meggitt-speedsys-300-rack-installation-730x549.jpg\" alt=\"\" width=\"730\" height=\"549\" srcset=\"https://img.istec.com/2026/04/a3a71656-thyssengas-meggitt-speedsys-300-rack-installation-730x549.jpg 730w, https://img.istec.com/2026/04/a3a71656-thyssengas-meggitt-speedsys-300-rack-installation-300x226.jpg 300w, https://img.istec.com/2026/04/a3a71656-thyssengas-meggitt-speedsys-300-rack-installation-768x578.jpg 768w, https://img.istec.com/2026/04/a3a71656-thyssengas-meggitt-speedsys-300-rack-installation-1536x1156.jpg 1536w, https://img.istec.com/2026/04/a3a71656-thyssengas-meggitt-speedsys-300-rack-installation-2048x1542.jpg 2048w\" sizes=\"auto, (max-width: 730px) 100vw, 730px\" />Deliverables</h2>\n<ul>\n<li>1-on-1 replacement solutions without the need for infrastructural adjustments</li>\n<li>Extensive full proof-testing of the overspeed detection systems, while negating the need for actual overspeed situations</li>\n<li>Full scope supply and support of speed hardware, installation and testing</li>\n<li>Fast troubleshooting, delivery, installation and commissioning</li>\n<li>SIL3 certified overspeed detection system with a proof-test interval of 10+ years</li>\n</ul>\n<h2>Impact</h2>\n<p>With the Istec SpeedSys 300 rack installations Thyssengas has a reliable overspeed detection system (SIL3) with a long proof-test interval. The replacement of the FT3000 rack with the SpeedSys 300 racks was successful, and benefits the reliability and availability of the gas turbines that drive the compressors.</p>\n<div class=\"gray-content-container\">\n<p><span class=\"alt-link\" style=\"color: #000000;\"></p>\n<div class='content-column one_third'><span class=\"alt-link\"><a href=\"https://www.istec.com/ar/download-the-speedsys-product-brochure/\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-33453 alignleft\" src=\"https://img.istec.com/2025/05/811bbf07-istec-speedsys-overspeed-protection-monitoring-300x184.png\" alt=\"\" width=\"183\" height=\"112\" srcset=\"https://img.istec.com/2025/05/811bbf07-istec-speedsys-overspeed-protection-monitoring-300x184.png 300w, https://img.istec.com/2025/05/811bbf07-istec-speedsys-overspeed-protection-monitoring.png 500w\" sizes=\"auto, (max-width: 183px) 100vw, 183px\" /></a></span></div>\n<div class='content-column two_third last_column'></span><span class=\"alt-link\" style=\"color: #000000;\"><span style=\"color: #00a88e;\"><strong>Product brochure &#8211; Speed hardware for gas turbines<br />\n</strong></span></span><span class=\"alt-link\" style=\"color: #000000;\">The speed product brochure provides a complete overview of our tachometers, overspeed detection systems, and speed sensors.</span></p>\n<p><span class=\"alt-link\" style=\"color: #000000;\"><span class=\"alt-link\"><a href=\"https://www.istec.com/ar/download-the-speedsys-product-brochure/\">Download our Driven By Speed Brochure »</a></span></span></div>\n<div class='clear_column'></div>\n</p>\n</div>\n","protected":false},"excerpt":{"rendered":"<p>Proof-testing overspeed detection systems (ODS) and replacing Jaquet FT3000 ODS with Istec SpeedSys 300 at a gas compressor station in Germany Thyssengas is one of the leading gas transmission system operators in Germany. At their plant in Elten they operate two gas turbines that drive two gas compressors to maintain the pressure of the gas &hellip; </p>\n","protected":false},"author":3,"featured_media":26469,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[98],"topics":[243,262,264],"class_list":["post-26468","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-uncategorized","topics-gas-turbines","topics-case-study","topics-speed"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.7 - https://yoast.com/product/yoast-seo-wordpress/ -->\n<title>Customer reference Thyssengas: Overspeed detection system replacement &#8212; Istec</title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" />\n<link rel=\"canonical\" href=\"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/\" />\n<meta property=\"og:locale\" content=\"ar_AR\" />\n<meta property=\"og:type\" content=\"article\" />\n<meta property=\"og:title\" content=\"Customer reference Thyssengas: Overspeed detection system replacement &#8212; Istec\" />\n<meta property=\"og:description\" content=\"Proof-testing overspeed detection systems (ODS) and replacing Jaquet FT3000 ODS with Istec SpeedSys 300 at a gas compressor station in Germany Thyssengas is one of the leading gas transmission system operators in Germany. At their plant in Elten they operate two gas turbines that drive two gas compressors to maintain the pressure of the gas &hellip;\" />\n<meta property=\"og:url\" content=\"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/\" />\n<meta property=\"og:site_name\" content=\"Istec\" />\n<meta property=\"article:published_time\" content=\"2023-03-24T08:41:57+00:00\" />\n<meta property=\"article:modified_time\" content=\"2026-07-24T08:41:41+00:00\" />\n<meta property=\"og:image\" content=\"https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x270-1.jpg?q=65\" />\n\t<meta property=\"og:image:width\" content=\"730\" />\n\t<meta property=\"og:image:height\" content=\"270\" />\n\t<meta property=\"og:image:type\" content=\"image/jpeg\" />\n<meta name=\"author\" content=\"istecadmin\" />\n<meta name=\"twitter:card\" content=\"summary_large_image\" />\n<meta name=\"twitter:label1\" content=\"Written by\" />\n\t<meta name=\"twitter:data1\" content=\"istecadmin\" />\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" />\n\t<meta name=\"twitter:data2\" content=\"4 minutes\" />\n<script type=\"application/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\/\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/#article\",\"isPartOf\":{\"@id\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/\"},\"author\":{\"name\":\"istecadmin\",\"@id\":\"https:\\/\\/www.istec.com\\/#\\/schema\\/person\\/04b7a48a774cc6803bde480e419841db\"},\"headline\":\"Customer reference Thyssengas: Overspeed detection system replacement\",\"datePublished\":\"2023-03-24T08:41:57+00:00\",\"dateModified\":\"2026-07-24T08:41:41+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/\"},\"wordCount\":600,\"publisher\":{\"@id\":\"https:\\/\\/www.istec.com\\/#organization\"},\"image\":{\"@id\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\/\\/img.istec.com\\/2023\\/03\\/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x270-1.jpg?q=65\",\"inLanguage\":\"ar-SA\"},{\"@type\":\"WebPage\",\"@id\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/\",\"url\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/\",\"name\":\"Customer reference Thyssengas: Overspeed detection system replacement &#8212; Istec\",\"isPartOf\":{\"@id\":\"https:\\/\\/www.istec.com\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\/\\/img.istec.com\\/2023\\/03\\/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x270-1.jpg?q=65\",\"datePublished\":\"2023-03-24T08:41:57+00:00\",\"dateModified\":\"2026-07-24T08:41:41+00:00\",\"breadcrumb\":{\"@id\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/#breadcrumb\"},\"inLanguage\":\"ar-SA\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"ar-SA\",\"@id\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/#primaryimage\",\"url\":\"https:\\/\\/img.istec.com\\/2023\\/03\\/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x270-1.jpg?q=65\",\"contentUrl\":\"https:\\/\\/img.istec.com\\/2023\\/03\\/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x270-1.jpg?q=65\",\"width\":730,\"height\":270},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\/\\/www.istec.com\\/customer-reference-thyssengas-overspeed-detection-system-replacement\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\/\\/www.istec.com\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Customer reference Thyssengas: Overspeed detection system replacement\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\/\\/www.istec.com\\/#website\",\"url\":\"https:\\/\\/www.istec.com\\/\",\"name\":\"Istec\",\"description\":\"\",\"publisher\":{\"@id\":\"https:\\/\\/www.istec.com\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\/\\/www.istec.com\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"ar-SA\"},{\"@type\":\"Organization\",\"@id\":\"https:\\/\\/www.istec.com\\/#organization\",\"name\":\"Istec\",\"url\":\"https:\\/\\/www.istec.com\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"ar-SA\",\"@id\":\"https:\\/\\/www.istec.com\\/#\\/schema\\/logo\\/image\\/\",\"url\":\"https:\\/\\/img.istec.com\\/2018\\/01\\/istec-international-logo.jpg?q=65\",\"contentUrl\":\"https:\\/\\/img.istec.com\\/2018\\/01\\/istec-international-logo.jpg?q=65\",\"width\":83,\"height\":88,\"caption\":\"Istec\"},\"image\":{\"@id\":\"https:\\/\\/www.istec.com\\/#\\/schema\\/logo\\/image\\/\"}},{\"@type\":\"Person\",\"@id\":\"https:\\/\\/www.istec.com\\/#\\/schema\\/person\\/04b7a48a774cc6803bde480e419841db\",\"name\":\"istecadmin\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"ar-SA\",\"@id\":\"https:\\/\\/secure.gravatar.com\\/avatar\\/ef2104d69abb108ecc953f2504e75cff42eef5e48ce6e93be2b0814a1056f0aa?s=96&d=mm&r=g\",\"url\":\"https:\\/\\/secure.gravatar.com\\/avatar\\/ef2104d69abb108ecc953f2504e75cff42eef5e48ce6e93be2b0814a1056f0aa?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\/\\/secure.gravatar.com\\/avatar\\/ef2104d69abb108ecc953f2504e75cff42eef5e48ce6e93be2b0814a1056f0aa?s=96&d=mm&r=g\",\"caption\":\"istecadmin\"},\"url\":\"https:\\/\\/www.istec.com\\/specialist\\/istecadmin\\/\"}]}</script>\n<!-- / Yoast SEO plugin. -->","yoast_head_json":{"title":"مرجع العميل Thyssengas: استبدال نظام الكشف عن السرعة الزائدة — Istec","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/","og_locale":"ar_AR","og_type":"article","og_title":"Customer reference Thyssengas: Overspeed detection system replacement &#8212; Istec","og_description":"Proof-testing overspeed detection systems (ODS) and replacing Jaquet FT3000 ODS with Istec SpeedSys 300 at a gas compressor station in Germany Thyssengas is one of the leading gas transmission system operators in Germany. At their plant in Elten they operate two gas turbines that drive two gas compressors to maintain the pressure of the gas &hellip;","og_url":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/","og_site_name":"Istec","article_published_time":"2023-03-24T08:41:57+00:00","article_modified_time":"2026-07-24T08:41:41+00:00","og_image":[{"width":730,"height":270,"url":"https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x270-1.jpg?q=65","type":"image/jpeg"}],"author":"istecadmin","twitter_card":"summary_large_image","twitter_misc":{"Written by":"istecadmin","Est. reading time":"4 minutes"},"schema":{"@context":"https://schema.org","@graph":[{"@type":"Article","@id":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/#article","isPartOf":{"@id":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/"},"author":{"name":"istecadmin","@id":"https://www.istec.com/ar/#/schema/person/04b7a48a774cc6803bde480e419841db"},"headline":"Customer reference Thyssengas: Overspeed detection system replacement","datePublished":"2023-03-24T08:41:57+00:00","dateModified":"2026-07-24T08:41:41+00:00","mainEntityOfPage":{"@id":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/"},"wordCount":600,"publisher":{"@id":"https://www.istec.com/ar/#organization"},"image":{"@id":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/#primaryimage"},"thumbnailUrl":"https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x270-1.jpg?q=65","inLanguage":"ar-SA"},{"@type":"WebPage","@id":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/","url":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/","name":"Customer reference Thyssengas: Overspeed detection system replacement &#8212; Istec","isPartOf":{"@id":"https://www.istec.com/ar/#website"},"primaryImageOfPage":{"@id":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/#primaryimage"},"image":{"@id":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/#primaryimage"},"thumbnailUrl":"https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x270-1.jpg?q=65","datePublished":"2023-03-24T08:41:57+00:00","dateModified":"2026-07-24T08:41:41+00:00","breadcrumb":{"@id":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/#breadcrumb"},"inLanguage":"ar-SA","potentialAction":[{"@type":"ReadAction","target":["https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/"]}]},{"@type":"ImageObject","inLanguage":"ar-SA","@id":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/#primaryimage","url":"https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x270-1.jpg?q=65","contentUrl":"https://img.istec.com/2023/03/Thyssengas-ft3000-replaced-by-meggitt-speedsys-300-730x270-1.jpg?q=65","width":730,"height":270},{"@type":"BreadcrumbList","@id":"https://www.istec.com/ar/customer-reference-thyssengas-overspeed-detection-system-replacement/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https://www.istec.com/ar/"},{"@type":"ListItem","position":2,"name":"Customer reference Thyssengas: Overspeed detection system replacement"}]},{"@type":"WebSite","@id":"https://www.istec.com/ar/#website","url":"https://www.istec.com/ar/","name":"Istec","description":"","publisher":{"@id":"https://www.istec.com/ar/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https://www.istec.com/ar/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"ar-SA"},{"@type":"Organization","@id":"https://www.istec.com/ar/#organization","name":"Istec","url":"https://www.istec.com/ar/","logo":{"@type":"ImageObject","inLanguage":"ar-SA","@id":"https://www.istec.com/ar/#/schema/logo/image/","url":"https://img.istec.com/2018/01/istec-international-logo.jpg?q=65","contentUrl":"https://img.istec.com/2018/01/istec-international-logo.jpg?q=65","width":83,"height":88,"caption":"Istec"},"image":{"@id":"https://www.istec.com/ar/#/schema/logo/image/"}},{"@type":"Person","@id":"https://www.istec.com/ar/#/schema/person/04b7a48a774cc6803bde480e419841db","name":"istecadmin","image":{"@type":"ImageObject","inLanguage":"ar-SA","@id":"https://secure.gravatar.com/avatar/ef2104d69abb108ecc953f2504e75cff42eef5e48ce6e93be2b0814a1056f0aa?s=96&d=mm&r=g","url":"https://secure.gravatar.com/avatar/ef2104d69abb108ecc953f2504e75cff42eef5e48ce6e93be2b0814a1056f0aa?s=96&d=mm&r=g","contentUrl":"https://secure.gravatar.com/avatar/ef2104d69abb108ecc953f2504e75cff42eef5e48ce6e93be2b0814a1056f0aa?s=96&d=mm&r=g","caption":"istecadmin"},"url":"https://www.istec.com/ar/specialist/istecadmin/"}]}},"_links":{"self":[{"href":"https://www.istec.com/ar/wp-json/wp/v2/posts/26468","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https://www.istec.com/ar/wp-json/wp/v2/posts"}],"about":[{"href":"https://www.istec.com/ar/wp-json/wp/v2/types/post"}],"author":[{"embeddable":true,"href":"https://www.istec.com/ar/wp-json/wp/v2/users/3"}],"replies":[{"embeddable":true,"href":"https://www.istec.com/ar/wp-json/wp/v2/comments?post=26468"}],"version-history":[{"count":29,"href":"https://www.istec.com/ar/wp-json/wp/v2/posts/26468/revisions"}],"predecessor-version":[{"id":37475,"href":"https://www.istec.com/ar/wp-json/wp/v2/posts/26468/revisions/37475"}],"wp:featuredmedia":[{"embeddable":true,"href":"https://www.istec.com/ar/wp-json/wp/v2/media/26469"}],"wp:attachment":[{"href":"https://www.istec.com/ar/wp-json/wp/v2/media?parent=26468"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https://www.istec.com/ar/wp-json/wp/v2/categories?post=26468"},{"taxonomy":"topics","embeddable":true,"href":"https://www.istec.com/ar/wp-json/wp/v2/topics?post=26468"}],"curies":[{"name":"wp","href":"https://api.w.org/{rel}","templated":true}]}}